ORCID
https://orcid.org/0000-0001-7772-083X
Abstract
Single-sided ventilation is a frequently employed ventilation strategy in contemporary structures, yet its effectiveness is often mediocre, underscoring the need for solutions to enhance its performance. To evaluate the effect of louvres and guide vanes on the effective ventilation rate, 21 different louvre configurations and four guide vane designs were compared with a plain opening for single-sided ventilation in a full-scale experimental test chamber under three different magnitudes of local wind velocity. Ventilation rates were measured using the tracer gas decay method with 12 NDIR CO2 sensors. The findings, obtained under specific test conditions, indicate that deeper openings result in a decline in ventilation rate performance. It was observed that wider guide vanes lead to higher ventilation rates, suggesting their potential to enhance SSV performance. The results reveal that, in most cases, louvres contribute to a decline in the system's performance. However, the ventilation rate is influenced by the angle and number of louvres, with optimal performance observed at specific angles and fewer louvres. These findings provide valuable insights for optimizing the design of airflow-guiding components in wind-driven single-sided ventilation systems, enabling the development of more efficient and customized solutions for natural ventilation in buildings.
Disciplines
Engineering | Power and Energy
DOI
10.1016/j.enbuild.2023.113627
Full Publication Date
October 2023
Publisher
Elsevier
Funder Name 1
Science Foundation Ireland
Award Number 1
12/RC/2302_P2
Funder Name 2
UK Engineering and Physical Sciences Research Council
Award Number 2
12/RC/2302_P2
Resource Type
journal article
Access Rights
open access
License Condition

This work is licensed under a Creative Commons Attribution 4.0 International License.
Alternative Identifier
https://www.sciencedirect.com/science/article/pii/S0378778823008575?via%3Dihub
Recommended Citation
Nima Najafi Ziarani, Malcolm J. Cook, Paul D. O'Sullivan,, Experimental evaluation of airflow guiding components for wind-driven single-sided natural ventilation: A comparative study in a test chamber, Energy and Buildings, Volume 300, 2023, 113627, https://doi.org/10.1016/j.enbuild.2023.113627.
Publication Details
Energy and Buildings, vol. 300, December 2023.